9.2.7 Protection of Class 1 buildings—separation of Class 10a buildings on an allotment
Part 9.2 Fire separation of external walls · NCC 2019: Figure 3.7.2.6
The following methods are acceptable for the protection of a Class 1 building where two or more Class 10a buildings on the same allotment are located between and are associated with different Class 1 buildings:
Each Class 10a building must be separated from each other by a distance of not less than 1.8 m, as shown in Figure 9.2.7a.
Each Class 10a building must be separated from each other by external walls complying with 9.2.3, as shown in Figure 9.2.7b.
Each Class 10a building must be separated from each Class 1 building by a distance of not less than 900 mm, as shown in Figure 9.2.7c.
Each Class 10a building must be separated from each Class 1 building by external walls complying with 9.2.3, as shown in Figure 9.2.7d.
Each Class 10a building must be separated by a wall complying with 9.3.1, as shown in Figure 9.2.7e.
Each Class 10a building must be separated from each other by external walls complying with 9.2.3, as shown in Figure 9.2.7f.
Each Class 10a building must be separated from each Class 1 building by external walls complying with 9.2.3, as shown in Figure 9.2.7g.
Each Class 10a building must be separated by a wall complying with 9.3.1, as shown in Figure 9.2.7h.
Figure 9.2.7a 1.8m separation between Class 10a buildings
Figure 9.2.7b External wall to Class 10a building with FRL (method 1)
Figure 9.2.7c 900 mm separation between Class 10a and Class 1 buildings
Figure 9.2.7d External wall to a Class 10a buildings with FRL (method 2)
Figure 9.2.7e Class 10a buildings with FRL to separating wall (method 1)
Figure 9.2.7f External wall to adjacent Class 10a buildings with FRL (method 1)
Figure 9.2.7g External wall to adjacent Class 10a buildings with FRL (method 2)
Figure 9.2.7h Class 10a buildings with FRL to separating wall (method 2)