9.3.4 Horizontal projections

Part 9.3 Fire protection of separating walls and floors · NCC 2019: 3.7.3.5

Open 9.3.4 on NCC Online ↗

(1) Where a horizontal projection forms part of a separating wall complying with 9.3.1, any horizontal projection within 1.8 m on each side of the separating wall (see Figure 9.3.4) must—

be a floor/ceiling or floor/soffit system incorporating a ceiling or soffit which has a resistance to the incipient spread of fire to the space above itself of not less than 60 minutes; or

have an FRL not less than 30/30/30 when tested from the underside; or

have a fire-protective covering on the underside of the floor, including beams incorporated in it, if the floor is combustible or of metal.

(2) The part of the separating wall that projects outwards horizontally must—

extend to the underside of the floor/ceiling or floor/soffit system complying with (1); and

not be crossed by timber or other combustible building elements except for framing members with dimensions of 75 x 50 mm or less, or sarking; and

have any gap between the bottom of the wall and the underside of the floor/ceiling or floor/soffit system packed with mineral fibre or other suitable fire-resisting material.

(3) Where a floor subject to (1)(b) depends on direct vertical or lateral support from another part to maintain its FRL, that supporting part must have an FRL of not less than 30/-/-.

(4) Where a service passes through a floor referred to in (1), the penetration must not reduce the fire performance of the floor or covering.

Figure 9.3.4 Horizontal projection forming part of a separating wall

Figure Notes

Horizontal projections within 1.8 m of another building must be protected in accordance with 9.3.4(1).

Same wording in ABCB Housing Provisions 2025. See ABCB Housing Provisions 2025 9.3.4.