Housing Provisions clause · ABCB Housing Provisions 2022

9.3.3 Roof lights

Part 9.3 Fire protection of separating walls and floors · NCC 2019: 3.7.3.4

Open 9.3.3 on NCC Online ↗

Combustible roof lights, skylights or the like installed in a roof or part of a roof required to have a non-combustible covering must—

have an aggregate area not more than 20% of the roof or part of the roof; and

be not less than 900 mm from the vertical projection of a separating wall extending to the underside of the roof covering.

Same wording in ABCB Housing Provisions 2025. See ABCB Housing Provisions 2025 9.3.3.

Defined terms used