NSW 13.2.6 Floors and subfloor walls

Part 13.2 Building fabric · varies 13.2.6 Floors and subfloor walls

Open on NCC Online ↗

Delete clause 13.2.6 and insert NSW 13.2.6 as follows:

(1) A concrete slab-on-ground with an in-slab or in-screed heating or cooling system, must have insulation with an R-Value greater than or equal to 1.0, installed around the vertical edge of its perimeter.

(2) Insulation required by (1) must—

be water resistant; and

be continuous from the adjacent finished ground level—

to a depth of greater than or equal to 300 mm; or

for at least the full depth of the vertical edge of the concrete slab-on-ground (see Figure 13.2.6).

(3) The requirements of (1) do not apply to an in-screed heating or cooling system used solely in a bathroom, amenity area or the like.

Figure 13.2.6 Insulation of slab edge

Not in NCC 2025. No NSW 13.2.6 in ABCB Housing Provisions 2025.