Housing Provisions clause · ABCB Housing Provisions 2022

13.2.6 Floors and subfloor walls

Part 13.2 Building fabric · NCC 2019: NSW 3.12.1.1, 3.12.1.5

Open 13.2.6 on NCC Online ↗
Varied in NSW, NT. Check the variation for your state.

(1) Floor insulation, where the floor is over an unenclosed space, must achieve the minimum R-Value in accordance with Table 13.2.6a.

(2) Floor and subfloor insulation, where the floor is over an enclosed subfloor space, must—

in climate zone 1, be subfloor wall insulation with an R-Value of R1.5; and

in climate zone 2, be subfloor wall insulation in accordance with Table 13.2.6b; and

in climate zone 3, be subfloor wall insulation in accordance with Table 13.2.6c; and

in climate zone 4, be in accordance with Table 13.2.6d; and

in climate zone 5, be in accordance with Table 13.2.6e; and

in climate zone 6, be in accordance with Table 13.2.6f; and

in climate zone 7, be in accordance with Table 13.2.6g; and

in climate zone 8, be in accordance with Table 13.2.6h.

(3) The thermal bridging in a metal-framed floor must be addressed by—

achieving the Total R-Value in Table 13.2.6i, calculated by—

using a method that accounts for the effect of thermal bridging in a suspended floor above an enclosed subfloor space; or

using AS/NZS 4859.2 for all other floors; or

complying with one of the options in Table 13.2.6j.

(4) A concrete slab-on-ground with an in-slab or in-screed heating or cooling system, must have insulation with an R-Value greater than or equal to 1.0, installed around the vertical edge of its perimeter.

(5) Except for a waffle-pod slab—

in climate zones 6 and 7—

insulation with R-Value greater than or equal to 0.64 must be installed around the vertical edge of its perimeter; and

insulation with an R-Value greater than or equal to 0.64 must be installed underneath the slab; and

in climate zone 8—

insulation with an R-Value greater than or equal to 1.0 must be installed around the vertical edge of its perimeter; and

insulation with an R-Value greater than or equal to 2.0 must be installed underneath the slab.

(6) Insulation required by (4), (5)(a)(i) and (5)(b)(i) must—

be water resistant; and

be continuous from the adjacent finished ground level—

to a depth of greater than or equal to 300 mm; or

for at least the full depth of the vertical edge of the concrete slab-on-ground (see Figure 13.2.6).

(7) The requirements of (4) do not apply to an in-screed heating or cooling system used solely in a bathroom, amenity area or the like.

Table 13.2.6a Minimum R-Value of floor insulation where the floor is over an unenclosed space

Climate zone

R-Value

1

2.0

2

2.0

3

1.5

4

X

5

X

6

4.0, or 3.5 if used in conjunction with a reflective airspace

7

8

Table Notes

R-Values listed are for the labelled, declared R-Value of insulation.

X = not permitted.

Table 13.2.6b Minimum R-Value of subfloor wall insulation where the floor is over an enclosed subfloor space: climate zone 2

Subfloor wall height (mm)

Minimum subfloor wall insulation R-Value

≤600

0.5

>600 to ≤900

1.0

>900 to ≤1200

1.5

>1200 to ≤1500

1.5

>1500 to ≤1800

1.5

Table Notes

Under-floor insulation is not permitted in climate zone 2.

R-Values listed are for the labelled, declared R-Value of insulation.

Subfloor wall insulation must not obstruct ventilation openings in the subfloor walls.

Table 13.2.6c Minimum R-Value of subfloor wall insulation where the floor is over an enclosed subfloor space: climate zone 3

Subfloor wall height (mm)

Minimum subfloor wall insulation R-Value

≤600

0.5

>600 to ≤900

0.5

>900 to ≤1200

0.5

>1200 to ≤1500

0.5

>1500 to ≤1800

0.5

Table Notes

Under-floor insulation is not permitted in climate zone 3.

R-Values listed are for the labelled, declared R-Value of insulation.

Subfloor wall insulation must not obstruct any ventilation openings in subfloor walls.

Table 13.2.6d Minimum R-Value of floor and subfloor wall insulation where the floor is over an enclosed subfloor space: climate zone 4

Subfloor wall height (mm)

Reflective insulation facing down over the subfloor space

Minimum subfloor wall insulation R-Value

Minimum suspended floor insulation R-Value

≤600

No

0.5

1.0

≤600

No

1.0

0.5

≤600

Yes

0.0

1.5

≤600

Yes

0.5

1.0

≤600

Yes

2.0

0.5

>600 to ≤900

No

0.0

1.5

>600 to ≤900

No

1.5

0.5

>600 to ≤900

Yes

0.0

1.5

>600 to ≤900

Yes

0.5

1.0

>900 to ≤1200

No

0.0

1.5

>900 to ≤1200

No

0.5

1.0

>900 to ≤1200

Yes

0.5

1.0

>900 to ≤1200

Yes

2.0

0.5

>1200 to ≤1500

No

0.0

1.5

>1200 to ≤1500

Yes

0.0

1.5

>1200 to ≤1500

Yes

0.5

1.0

>1500 to ≤1800

No

0.5

1.5

>1500 to ≤1800

No

1.0

1.0

>1500 to ≤1800

Yes

0.0

2.0

Table Notes

A suspended floor includes a suspended timber-framed floor, suspended metal-framed floor and suspended concrete floor.

R-Values listed are for the labelled, declared R-Value of insulation.

Table 13.2.6e Minimum R-Value of floor and subfloor wall insulation where the floor is over an enclosed subfloor area: climate zone 5

Subfloor wall height (mm)

Reflective insulation facing down over the subfloor surface

Minimum subfloor wall insulation R-Value

Minimum suspended floor insulation R-Value

≤600

No

0.0

1.5

≤600

Yes

0.0

2.0

>600 to ≤900

No

0.0

1.5

>600 to ≤900

Yes

0.0

2.0

>900 to ≤1200

No

0.0

2.0

>900 to ≤1200

Yes

0.0

2.0

>1200 to ≤1500

No

0.0

2.0

>1200 to ≤1500

Yes

0.0

2.0

>1500 to ≤1800

No

0.0

2.5

>1500 to ≤1800

No

0.5

2.0

>1500 to ≤1800

Yes

0.0

2.5

>1500 to ≤1800

Yes

0.5

2.0

Table Notes

A suspended floor includes a suspended timber-framed floor, a suspended metal-framed floor and a suspended concrete floor.

R-Values listed are for the labelled, declared R-Value of insulation.

Table 13.2.6f Minimum R-Value of floor and subfloor wall insulation where the floor is over an enclosed subfloor space: climate zone 6

Subfloor wall height (mm)

Reflective insulation facing down over the subfloor area

Minimum subfloor wall insulation R-Value

Minimum suspended floor insulation R-Value

≤600

No

0.0

2.0

≤600

Yes

0.0

1.5

>600 to ≤900

No

0.0

2.0

>600 to ≤900

Yes

0.0

1.5

>900 to ≤1200

No

0.0

2.0

>900 to ≤1200

Yes

0.0

1.5

>1200 to ≤1500

No

0.0

2.5

>1200 to ≤1500

No

0.5

2.0

>1200 to ≤1500

Yes

0.0

1.5

>1500 to ≤1800

No

0.0

2.5

>1500 to ≤1800

Yes

0.0

2.0

>1500 to ≤1800

Yes

0.5

1.5

Table Notes

A suspended floor includes a suspended timber-framed floor, suspended metal-framed floor and suspended concrete floor.

R-Values listed are for the labelled, declared R-Value of insulation.

Table 13.2.6g Minimum R-Value of floor and subfloor insulation where the floor is over an enclosed subfloor space: climate zone 7

Subfloor wall height (mm)

Reflective insulation facing down over the subfloor space

Minimum subfloor wall insulation R-Value

Minimum suspended floor insulation R-Value

≤600

No

0.0

2.5

≤600

Yes

0.0

1.5

>600 to ≤900

No

0.0

2.5

>600 to ≤900

Yes

0.0

1.5

>900 to ≤1200

No

0.0

3.0

>900 to ≤1200

Yes

0.0

1.5

>1200 to ≤1500

No

0.0

3.0

>1200 to ≤1500

Yes

0.0

1.5

>1500 to ≤1800

No

0.0

3.0

>1500 to ≤1800

Yes

1.0

1.5

>1500 to ≤1800

Yes

0.0

2.0

Table Notes

A suspended floor includes a suspended timber-framed floor, suspended metal-framed floor and suspended concrete floor.

R-Values listed are for the labelled, declared R-Value of insulation.

Table 13.2.6h Minimum R-Value of floor and subfloor wall insulation where the floor is over an enclosed subfloor space: climate zone 8

Subfloor wall height (mm)

Reflective insulation facing down over the subfloor space

Minimum subfloor wall insulation R-Value

Minimum suspended floor insulation R-Value

≤600

No

0.0

2.5

≤600

Yes

0.0

1.5

>600 to ≤900

No

0.0

2.5

>600 to ≤900

Yes

0.0

1.5

>900 to ≤1200

No

0.0

3.0

>900 to ≤1200

Yes

0.0

1.5

>1200 to ≤1500

No

0.0

3.0

>1200 to ≤1500

Yes

0.0

1.5

>1500 to ≤1800

No

0.0

3.0

>1500 to ≤1800

Yes

1.0

1.5

>1500 to ≤1800

Yes

0.0

2.0

Table Notes

A suspended floor includes a suspended timber-framed floor, suspended metal-framed floor and suspended concrete floor.

R-Values listed are for the labelled, declared R-Value of insulation.

Table 13.2.6i Metal-framed suspended floor — minimum Total R-Value for floor to account for thermal bridging

Floor insulation from Tables 13.2.6a and 13.2.6d to 13.2.6h as applicable

Floor covering

Minimum Total R-Value of floor

0.0

Carpet

0.36

0.0

Other

0.22

0.5

Carpet

0.86

0.5

Other

0.71

1.0

Carpet

1.30

1.0

Other

1.15

1.5

Carpet

1.65

1.5

Tables

Changed in NCC 2025. See ABCB Housing Provisions 2025 13.2.6, or show what changed.

(1) Floor insulation, where the floor is over an unenclosed … 1.0, installed around the vertical edge of its perimeter. (5) Except for A concrete slab-on-ground or the like, other than a waffle-pod slab — waffle pod slab, must be insulated in accordance with the following: In climate zones 6 and 7 — insulation with R-Value greater … than or equal to 0.64 must be installed underneath the slab; and in slab. In climate zone 8 — insulation with an R-Value greater than … Minimum Total R-Value of floor 0.0 Carpet 0.36 0.0 Other 0.22 0.5 Carpet 0.86 0.5 Other 0.71 1.0 Carpet 1.30 1.0 Other 1.15 1.5 Carpet 1.65 1.5