QLD 3.4.2 Termite management systems
Part 3.4 Termite risk management · varies 3.4.2 Termite management systems
Delete clause 3.4.2 and insert QLD 3.4.2 as follows:
Where a termite management system is required it must—
be selected appropriate to QLD Table 3.4.2; and
comply with—
AS 3660.1 subject to clauses QLD 3.4.1(4), (5) and (6); or
have been tested and passed the tests required by Section 5 of AS 3660.3; and
have a durable notice installed in accordance with 3.4.3; and
where a chemical termite management system is used, the chemical must be included on the appropriate authority’s pesticides register.
Insert QLD table (3.4.2) 3.4.2 as follows:
QLD Table 3.4.2: Acceptable termite management systems and components (per AS 3660.1)
Footing system
Slab edge exposure
Termite shielding
Stainless steel mesh
Graded stone
Chemicals
Concrete slab on ground complying with AS 2870: Penetrations and control joints
Not suitable
Not suitable
Component; or full system subject to 3.4.1(4)
Component; or full system subject to 3.4.1(4)
Full system beneath slab subject to 3.4.1(4) and (5)
Concrete slab on ground complying with AS 2870: Slab perimeter
Suitable subject to 3.4.1(4)
Not suitable
Component; or full system subject to 3.4.1(4)
Component; or full system subject to 3.4.1(4)
Perimeter system subject to 3.4.1(4) and (6)
Concrete slab on ground not complying with AS 2870: Beneath slab (includes penetrations and control joints)
Not suitable
Not suitable
Full system subject to 3.4.1(4)
Full system subject to 3.4.1(4)
Full system beneath slab subject to 3.4.1(4) and (5)
Concrete slab on ground not complying with AS 2870: Slab perimeter
Suitable subject to 3.4.1(4)
Not suitable
Full system subject to 3.4.1(4)
Full system subject to 3.4.1(4)
Perimeter system subject to 3.4.1(4) and (6)
Suspended floors
Not applicable
Suitable subject to 3.4.1(4)
Suitable subject to 3.4.1(4)
Component; or full system subject to 3.4.1(4)
Full system subject to 3.4.1(4)