Table · ABCB Housing Provisions 2022

Table 13.3.2n Orientation sector winter exposure factor (EW) — floor in direct contact with the ground: climate zone 7

Part 13.3 External glazing

Open Table 13.3.2n on NCC Online ↗
P/HNorthNorth eastEastSouth eastSouthSouth westWestNorth west
0.001.871.921.200.520.460.531.131.80
0.051.811.831.120.440.380.451.041.73
0.101.811.801.060.410.360.420.991.69
0.201.701.680.990.370.330.380.901.54
0.401.461.460.840.320.270.320.751.36
0.601.341.280.730.280.250.280.661.15
0.801.141.100.640.250.220.250.591.00
1.001.040.980.590.220.210.220.510.85
1.200.820.820.490.210.200.210.450.76
1.400.750.800.480.190.180.200.410.58
1.600.580.580.440.180.170.170.380.54
1.800.470.550.350.170.170.170.350.47
2.000.350.460.350.150.160.170.300.40

Table Notes

For P/H between those shown in this Table, either use the next highest P/H or interpolate.

Table for 13.3.2 External glazing — winter

Same wording in ABCB Housing Provisions 2025. See ABCB Housing Provisions 2025 Table 13.3.2n.