Table · ABCB Housing Provisions 2022
Table 13.3.2x Orientation sector conductance factor (OC): climate zone 7
| Floor type | North | North east | East | South east | South | South west | West | North west |
|---|---|---|---|---|---|---|---|---|
| Floor in direct contact with the ground | 1.30 | 1.05 | 0.80 | 0.80 | 0.80 | 0.80 | 0.80 | 1.05 |
| Suspended floor | 1.30 | 1.10 | 0.90 | 0.90 | 0.90 | 0.90 | 0.90 | 1.10 |
Table for 13.3.2 External glazing — winter