Table · ABCB Housing Provisions 2022

Table 6.3.4i Maximum combined strutting/hanging beam span — combined strutting/hanging beam supporting tiled roof and plasterboard ceiling — roof load area = 12 m2

Part 6.3 Structural steel members

Open Table 6.3.4i on NCC Online ↗
SectionCeiling load width (m)
1.83.66.0
125 TFB1.71.71.7
150 UB 14.01.81.81.8
200 UB 18.22.42.42.4
250 UB 31.43.83.83.7
310 UB 46.25.05.04.9
100 TFB0.90.90.9
150 PFC2.42.42.3
200 PFC2.92.82.8
250 PFC4.04.03.9
300 PFC4.34.24.2

Table Notes

Load accounted for includes 0.2 kPa permanent ceiling, 0.84 kPa permanent roof, permanent member self-weight, 0.25 kPa imposed roof, positive roof wind pressure of 0.95 kPa and negative roof wind pressure of -1.49 kPa.

Load combinations included are 1.35G, 1.2G + 1.5Q, 1.2G + WU + 0.4Q, 0.9G + WU for ULS and G + 0.7Q, G + WS.

0.9G + WS for SLS with a maximum deflection of span/300.

Strutting beams are assumed to be partially restrained at both ends with no rotational restraint and are designed as members without full lateral restraint.

Table for 6.3.4 Strutting beams

Same wording in ABCB Housing Provisions 2025. See ABCB Housing Provisions 2025 Table 6.3.4i.