Housing Provisions clause · ABCB Housing Provisions 2022

6.3.4 Strutting beams

Part 6.3 Structural steel members

Open 6.3.4 on NCC Online ↗

Structural steel strutting beams must comply with the following:

Acceptable strutting beam spacing must be determined in accordance with—

for single span rafters — Table H1D6a and Figure H1D6a; and

for continuous span rafters — Table H1D6b and Figure H1D6b.

Maximum acceptable strutting beam spans must be determined in accordance with—

for metal sheet roofs — Tables 6.3.4a, 6.3.4b, 6.3.4c, 6.3.4d, 6.3.4e or 6.3.4f; and

for tiled roofs — Tables 6.3.4g, 6.3.4h, 6.3.4i, 6.3.4j, 6.3.4k or 6.3.4l.

Any point load applied must be located within the middle third of the strutting beam.

Strutting beams must be tied down in accordance with H1D6(3) where supporting metal roofs.

Fixing and any cutting of strutting beams must comply with 6.3.7.

Strutting beams must be supported by structural steel columns that comply with 6.3.6 and be fixed in accordance with 6.3.7.

Table 6.3.4a Maximum combined strutting/hanging beam span — combined strutting/hanging beam supporting metal sheet roof and plasterboard ceiling — roof load area = 4 m2

Section

Ceiling load width (m)

1.8

3.6

6.0

125 TFB

3.5

3.3

3.2

150 UB 14.0

3.6

3.4

3.3

200 UB 18.2

4.5

4.3

4.1

250 UB 31.4

6.8

6.5

6.2

310 UB 46.2

8.9

8.5

8.1

100 TFB

2.0

2.0

1.9

150 PFC

4.7

4.5

4.3

200 PFC

5.5

5.3

5.0

250 PFC

7.5

7.1

6.8

300 PFC

7.8

7.5

7.1

Table Notes

Load accounted for includes 0.2 kPa permanent ceiling, 0.4 kPa permanent roof, permanent member self-weight, 0.25 kPa imposed roof, positive roof wind pressure of 0.95 kPa and negative roof wind pressure of -1.49 kPa.

Load combinations included are 1.35G, 1.2G + 1.5Q, 1.2G + WU + 0.4Q, 0.9G + WU for ULS and G + 0.7Q, G + WS.

0.9G + WS for SLS with a maximum deflection of span/300.

Strutting beams are assumed to be partially restrained at both ends with no rotational restraint and are designed as members without full lateral restraint.

Table 6.3.4b Maximum combined strutting/hanging beam span — combined strutting/hanging beam supporting metal sheet roof and plasterboard ceiling — roof load area = 8 m2

Section

Ceiling load width (m)

1.8

3.6

6.0

125 TFB

2.6

2.6

2.5

150 UB 14.0

2.8

2.7

2.7

200 UB 18.2

3.6

3.5

3.4

250 UB 31.4

5.5

5.4

5.2

310 UB 46.2

7.3

7.1

6.9

100 TFB

1.4

1.4

1.4

150 PFC

3.7

3.6

3.5

200 PFC

4.4

4.3

4.1

250 PFC

6.0

5.8

5.7

300 PFC

6.3

6.2

6.0

Table Notes

Load accounted for includes 0.2 kPa permanent ceiling, 0.4 kPa permanent roof, permanent member self-weight, 0.25 kPa imposed roof, positive roof wind pressure of 0.95 kPa and negative roof wind pressure of -1.49 kPa.

Load combinations included are 1.35G, 1.2G + 1.5Q, 1.2G + WU + 0.4Q, 0.9G + WU for ULS and G + 0.7Q, G + WS.

0.9G + WS for SLS with a maximum deflection of span/300.

Strutting beams are assumed to be partially restrained at both ends with no rotational restraint and are designed as members without full lateral restraint.

Table 6.3.4c Maximum combined strutting/hanging beam span — combined strutting/hanging beam supporting metal sheet roof and plasterboard ceiling — roof load area = 12 m2

Section

Ceiling load width (m)

1.8

3.6

6.0

125 TFB

2.2

2.2

2.2

150 UB 14.0

2.4

2.3

2.3

200 UB 18.2

3.1

3.0

3.0

250 UB 31.4

4.8

4.7

4.6

310 UB 46.2

6.4

6.3

6.1

100 TFC

1.1

1.1

1.1

150 PFC

3.1

3.1

3.0

200 PFC

3.7

3.7

3.6

250 PFC

5.2

5.1

5.0

300 PFC

5.5

5.4

5.3

Table Notes

Load accounted for includes 0.2 kPa permanent ceiling, 0.4 kPa permanent roof, permanent member self-weight, 0.25 kPa imposed roof, positive roof wind pressure of 0.95 kPa and negative roof wind pressure of -1.49 kPa.

Load combinations included are 1.35G, 1.2G + 1.5Q, 1.2G + WU + 0.4Q, 0.9G + WU for ULS and G + 0.7Q, G + WS.

0.9G + WS for SLS with a maximum deflection of span/300.

Strutting beams are assumed to be partially restrained at both ends with no rotational restraint and are designed as members without full lateral restraint.

Table 6.3.4d Maximum counter-strutting beam span — counter-strutting beam supporting metal sheet roof and plasterboard ceiling — roof load area = 4 m2

Section

Ceiling load area (m2)

0

6

12

125 TFB

3.9

3.5

3.2

150 UB 14.0

4.0

3.7

3.4

200 UB 18.2

5.4

4.9

4.6

250 UB 31.4

8.9

8.2

7.7

310 UB 46.2

12.0

11.3

10.7

100 TFB

2.0

1.8

1.6

150 PFC

5.9

5.3

4.9

200 PFC

7.1

6.5

6.0

250 PFC

10.1

9.3

8.7

300 PFC

10.5

9.8

9.2

Table Notes

Load accounted for includes 0.2 kPa permanent ceiling, 0.4 kPa permanent roof, permanent member self-weight, 0.25 kPa imposed roof, positive roof wind pressure of 0.95 kPa and negative roof wind pressure of -1.49 kPa.

Load combinations included are 1.35G and 1.25G + 1.5Q, 1.25G + WU + 0.4Q, 0.9G + WU for ULS and G + 0.7Q, G+WS.

0.9G + WS for SLS with a maximum deflection of span/300.

Strutting beams are assumed to be partially restrained at both ends with no rotational restraint and are designed as members without full lateral restraint.

A ceiling load area of “0” must be used for strutting beams not supporting ceiling loads.

Table 6.3.4e Maximum counter-strutting beam span — counter-strutting beam supporting metal sheet roof and plasterboard ceiling — roof load area = 8 m2

Section

Ceiling load area (m2)

0

6

12

125 TFB

2.7

2.6

2.4

150 UB 14.0

2.9

2.8

2.6

200 UB 18.2

4.0

3.8

3.6

250 UB 31.4

6.8

6.5

6.2

310 UB 46.2

9.6

9.2

8.8

100 TFB

1.4

1.3

1.2

150 PFC

4.2

4.0

3.8

200 PFC

5.2

4.9

4.7

250 PFC

7.7

7.3

7.0

300 PFC

8.2

7.8

7.5

Table Notes

Load accounted for includes 0.2 kPa permanent ceiling, 0.4 kPa permanent roof, permanent member self-weight, 0.25 kPa imposed roof, positive roof wind pressure of 0.95 kPa and negative roof wind pressure of -1.49 kPa.

Load combinations included are 1.35G and 1.25G + 1.5Q, 1.25G + WU + 0.4Q, 0.9G + WU for ULS and G + 0.7Q, G+WS.

0.9G + WS for SLS with a maximum deflection of span/300.

Strutting beams are assumed to be partially restrained at both ends with no rotational restraint and are designed as members without full lateral restraint.

A ceiling load area of “0” must be used for strutting beams not supporting ceiling loads.

Table 6.3.4f Maximum counter-strutting beam span — counter-strutting beam supporting metal sheet roof and plasterboard ceiling — roof load area = 12 m2

Section

Ceiling load area (m2)

0

6

12

125 TFB

2.2

2.1

2.0

150 UB 14.0

2.4

2.3

2.2

200 UB 18.2

3.3

3.2

3.0

250 UB 31.4

5.7

5.5

5.3

310 UB 46.2

8.2

7.9

7.7

100 TFB

1.1

1.0

1.0

150 PFC

3.4

3.2

3.1

200 PFC

4.2

4.1

3.9

250 PFC

6.4

6.2

6.0

300 PFC

6.9

6.6

6.4

Table Notes

Load accounted for includes 0.2 kPa permanent ceiling, 0.4 kPa permanent roof, permanent member self-weight, 0.25 kPa imposed roof, positive roof wind pressure of 0.95 kPa and negative roof wind pressure of -1.49 kPa.

Load combinations included are 1.35G and 1.25G + 1.5Q, 1.25G + WU + 0.4Q, 0.9G + WU for ULS and G + 0.7Q, G+WS.

0.9G + WS for SLS with a maximum deflection of span/300.

Strutting beams are assumed to be partially restrained at both ends with no rotational restraint and are designed as members without full lateral restraint.

A ceiling load area of “0” must be used for strutting beams not supporting ceiling loads.

Table 6.3.4g Maximum combined strutting/hanging beam span — combined strutting/hanging beam supporting tiled roof and plasterboard ceiling — roof load area = 4 m2

Section

Ceiling load width (m)

1.8

3.6

6.0

125 TFB

2.7

2.6

2.6

150 UB 14.0

2.8

2.8

2.7

200 UB 18.2

3.6

3.5

3.4

250 UB 31.4

5.5

5.4

5.2

310 UB 46.2

7.2

7.1

6.9

100 TFB

1.6

1.5

1.5

150 PFC

3.7

3.7

3.6

200 PFC

4.4

4.3

4.2

250 PFC

6.0

5.8

5.7

300 PFC

6.3

6.1

6.0

Table Notes

Load accounted for includes 0.2 kPa permanent ceiling, 0.84 kPa permanent roof, permanent member self-weight, 0.25 kPa imposed roof, positive roof wind pressure of 0.95 kPa and negative roof wind pressure of -1.49 kPa.

Load combinations included are 1.35G, 1.2G + 1.5Q, 1.2G + WU + 0.4Q, 0.9G + WU for ULS and G + 0.7Q, G + WS.

0.9G + WS for SLS with a maximum deflection of span/300.

Strutting beams are assumed to be partially restrained at both ends with no rotational restraint and are designed as members without full lateral restraint.

Table 6.3.4h Maximum combined strutting/hanging beam span

Tables

Same wording in ABCB Housing Provisions 2025. See ABCB Housing Provisions 2025 6.3.4.

Clauses referred to