Table · ABCB Housing Provisions 2022

Table 6.3.5f Maximum lintel span — lintel supporting tiled roof, tiled floor and 3 m high exterior wall — roof load width = 7.5 m

Part 6.3 Structural steel members

Open Table 6.3.5f on NCC Online ↗
SectionFloor load width (m)
01.83.6
150 UB 14.02.42.22.0
200 UB 25.43.83.43.2
250 UB 31.44.34.03.7
100 TFB1.51.31.2
150 PFC3.02.72.5
200 PFC3.43.12.9
250 PFC4.64.23.9
75 x 75 x 5 EA–––
90 x 90 x 6 EA–––
100 x 100 x 6 EA–––
125 x 75 x 6 UA1.0––
150 x 100 x 10 UA2.01.81.5

Table Notes

Load accounted for includes 0.98 kPa permanent floor, 1.16 kN/m permanent wall, 0.85 kPa permanent roof, permanent member self-weight, 1.5 kPa or 1.1 kN imposed floor, positive roof wind pressure of 0.95 kPa and negative roof wind pressure of -1.49 kPa.

Load combinations included are 1.35G, 1.2G + 1.5Q, 1.2G + WU + 0.4Q, 0.9G + WU for ULS G + 0.7Q, G + WS.

0.9G + WS for SLS with a maximum deflection of span/300.

Lintels are assumed to be partially restrained at both ends with no rotational restraint and are designed as members without full lateral restraint.

A floor load of “0” must be used for lintels not supporting floor loads.

Table for 6.3.5 Lintels

Same wording in ABCB Housing Provisions 2025. See ABCB Housing Provisions 2025 Table 6.3.5f.