Housing Provisions clause · ABCB Housing Provisions 2022

6.3.5 Lintels

Part 6.3 Structural steel members

Open 6.3.5 on NCC Online ↗

Structural steel lintels must comply with the following:

Spans for lintels supporting roofs, frames and timber floors must be determined in accordance with—

for metal sheet roofs, Table 6.3.5a, 6.3.5b or 6.3.5c; and

for tiled roofs, Table 6.3.5d, 6.3.5e or 6.3.5f.

Effective load widths for structural steel lintels must be determined in accordance with Figure 6.3.5 (a) or (b).

All loads along the structural steel lintel must be evenly distributed.

The top flange of the structural steel lintel must be laterally restrained at the loading points.

Fixing of structural steel lintels must comply with 6.3.7.

Structural steel lintels used in masonry must also comply with H1D5.

Lintel beams must be supported by structural steel columns that comply with 6.3.6.

Table 6.3.5a Maximum lintel span — lintel supporting metal sheet roof, timber floor and 3 m high exterior wall — roof load width = 1.5 m

Section

Floor load width (m)

0

1.8

3.6

150 UB 14.0

4.4

3.0

2.5

200 UB 25.4

6.8

4.7

4.0

250 UB 31.4

7.7

5.3

4.6

100 TFB

2.8

1.8

1.5

150 PFC

5.7

3.8

3.2

200 PFC

6.5

4.3

3.7

250 PFC

8.4

5.7

4.9

75 x 75 x 5 EA

2.0

1.0

–

90 x 90 x 6 EA

3.0

1.5

1.0

100 x 100 x 6 EA

3.0

1.8

1.0

125 x 75 x 6 UA

3.0

1.8

1.3

150 x 100 x 10 UA

4.0

3.0

2.5

Table Notes

Load accounted for includes 0.53 kPa permanent floor, 1.16 kN/m permanent wall, 0.4 kPa permanent roof, permanent member self-weight, 1.5 kPa or 1.1 kN imposed floor, positive roof wind pressure of 0.95 kPa and negative roof wind pressure of -1.49 kPa.

Load combinations included are 1.35G and 1.2G + 1.5Q, 1.2G + WU + 0.4Q, 0.9G + WU for ULS and G + 0.7Q, G + WS.

0.9G + WS for SLS with a maximum deflection of span/300.

Lintels are assumed to be partially restrained at both ends with no rotational restraint and are designed as members without full lateral restraint.

A floor load of “0” must be used for lintels not supporting floor loads.

Table 6.3.5b Maximum lintel span — lintel supporting metal sheet roof, timber floor and 3 m high exterior wall — roof load width = 4.5 m

Section

Floor load width (m)

0

1.8

3.6

150 UB 14.0

3.1

2.7

2.4

200 UB 25.4

4.9

4.3

3.8

250 UB 31.4

5.6

4.9

4.3

100 TFB

1.9

1.7

1.5

150 PFC

4.0

3.4

3.0

200 PFC

4.5

3.9

3.4

250 PFC

6.0

5.2

4.6

75 x 75 x 5 EA

1.0

–

–

90 x 90 x 6 EA

1.8

1.3

–

100 x 100 x 6 EA

1.8

1.3

–

125 x 75 x 6 UA

1.8

1.3

1.0

150 x 100 x 10 UA

3.0

2.5

2.0

Table Notes

Load accounted for includes 0.53 kPa permanent floor, 1.16 kN/m permanent wall, 0.4 kPa permanent roof, permanent member self-weight, 1.5 kPa or 1.1 kN imposed floor, positive roof wind pressure of 0.95 kPa and negative roof wind pressure of -1.49 kPa.

Load combinations included are 1.35G and 1.2G + 1.5Q, 1.2G + WU + 0.4Q, 0.9G + WU for ULS and G + 0.7Q, G + WS.

0.9G + WS for SLS with a maximum deflection of span/300.

Lintels are assumed to be partially restrained at both ends with no rotational restraint and are designed as members without full lateral restraint.

A floor load of “0” must be used for lintels not supporting floor loads.

Table 6.3.5c Maximum lintel span — lintel supporting metal sheet roof, timber floor and 3 m high exterior wall — roof load width = 7.5 m

Section

Floor load width (m)

0

1.8

3.6

150 UB 14.0

2.6

2.4

2.2

200 UB 25.4

4.1

3.8

3.6

250 UB 31.4

4.7

4.4

4.1

100 TFB

1.6

1.5

1.4

150 PFC

3.3

3.0

2.8

200 PFC

3.8

3.5

3.3

250 PFC

5.1

4.6

4.3

75 x 75 x 5 EA

–

–

–

90 x 90 x 6 EA

1.0

–

–

100 x 100 x 6 EA

1.0

–

–

125 x 75 x 6 UA

1.3

1.0

1.0

150 x 100 x 10 UA

2.5

2.0

2.0

Table Notes

Load accounted for includes 0.53 kPa permanent floor, 1.16 kN/m permanent wall, 0.4 kPa permanent roof, permanent member self-weight, 1.5 kPa or 1.1 kN imposed floor, positive roof wind pressure of 0.95 kPa and negative roof wind pressure of -1.49 kPa.

Load combinations included are 1.35G and 1.2G + 1.5Q, 1.2G + WU + 0.4Q, 0.9G + WU for ULS and G + 0.7Q, G + WS.

0.9G + WS for SLS with a maximum deflection of span/300.

Lintels are assumed to be partially restrained at both ends with no rotational restraint and are designed as members without full lateral restraint.

A floor load of “0” must be used for lintels not supporting floor loads.

Table 6.3.5d Maximum lintel span — lintel supporting tiled roof, tiled floor and 3 m high exterior wall — roof load width = 1.5 m

Section

Floor load width (m)

0

1.8

3.6

150 UB 14.0

4.0

2.8

2.3

200 UB 25.4

6.2

4.4

3.7

250 UB 31.4

7.1

5.0

4.3

100 TFB

2.5

1.7

1.4

150 PFC

5.2

3.5

2.9

200 PFC

5.9

4.0

3.4

250 PFC

7.7

5.4

4.5

75 x 75 x 5 EA

2.0

–

–

90 x 90 x 6 EA

2.5

1.3

–

100 x 100 x 6 EA

3.0

1.3

–

125 x 75 x 6 UA

2.5

1.5

1.0

150 x 100 x 10 UA

4.0

2.5

2.0

Table Notes

Load accounted for includes 0.98 kPa permanent floor, 1.16 kN/m permanent wall, 0.85 kPa permanent roof, permanent member self-weight, 1.5 kPa or 1.1 kN imposed floor, positive roof wind pressure of 0.95 kPa and negative roof wind pressure of -1.49 kPa.

Load combinations included are 1.35G, 1.2G + 1.5Q, 1.2G + WU + 0.4Q, 0.9G + WU for ULS G + 0.7Q, G + WS.

0.9G + WSS for SLS with a maximum deflection of span/300.

Lintels are assumed to be partially restrained at both ends with no rotational restraint and are designed as members without full lateral restraint.

A floor load of “0” must be used for lintels not supporting floor loads.

Table 6.3.5e Maximum lintel span — lintel supporting tiled roof, tiled floor and 3 m high exterior wall — roof load width = 4.5 m

Section

Floor load width (m)

0

1.8

3.6

150 UB 14.0

2.8

2.5

2.2

200 UB 25.4

4.4

3.9

3.5

250 UB 31.4

5.1

4.5

4.0

100 TFB

1.7

1.5

1.3

150 PFC

3.6

3.1

2.7

200 PFC

4.1

3.6

3.1

250 PFC

5.4

4.7

4.2

75 x 75 x 5 EA

–

–

–

90 x 90 x 6 EA

1.3

1.0

–

100 x 100 x 6 EA

1.5

1.0

–

125 x 75 x 6 UA

1.5

1.0

–

150 x 100 x 10 UA

2.5

2.0

1.8

Table Notes

Load accounted for includes 0.98 kPa permanent floor, 1.16 kN/m permanent wall, 0.85 kPa permanent roof, permanent member self-weight, 1.5 kPa or 1.1 kN imposed floor, positive roof wind pressure of 0.95 kPa and negative roof wind pressure of -1.49 kPa.

Load combinations included are 1.35G, 1.2G + 1.5Q, 1.2G + WU + 0.4Q, 0.9G + WU for ULS G + 0.7Q, G + WS.

0.9G + WS for SLS with a maximum deflection of span/300.

Lintels are assumed to be partially restrained at both ends with no rotational restraint and are designed as members without full lateral restraint.

A floor load of “0” must be used for lintels not supporting floor loads.

Table 6.3.5f Maximum lintel span — lintel supporting tiled roof, tiled floor and 3 m high exterior wall — roof load width = 7.5 m

Section

Floor load width (m)

0

1.8

3.6

150 UB 14.0

2.4

2.2

2.0

200 UB 25.4

3.8

3.4

3.2

250 UB 31.4

4.3

4.0

3.7

100 TFB

1.5

1.3

1.2

150 PFC

3.0

2.7

2.5

200 PFC

3.4

3.1

2.9

250 PFC

4.6

4.2

3.9

75 x 75 x 5 EA

–

–

–

90 x 90 x 6 EA

–

–

–

100 x 100 x 6 EA

–

–

–

125 x 75 x 6 UA

1.0

–

–

150 x 100 x 10 UA

2.0

1.8

1.5

Table Notes

Load accounted for includes 0.98 kPa permanent floor, 1.16 kN/m permanent wall, 0.85 kPa permanent roof, permanent member self-weight, 1.5 kPa or 1.1 kN imposed floor, positive roof wind pressure of 0.95 kPa and negative roof wind pressure of -1.49 kPa.

Load combinations included are 1.35G, 1.2G + 1.5Q, 1.2G + WU + 0.4Q, 0.9G + WU for ULS G + 0.7Q, G + WS.

0.9G + WS for SLS with a maximum deflection of span/300.

Lintels are assumed to be partially restrained at both ends with no rotational restraint and are designed as members without full lateral restraint.

A floor load of “0” must be used for lintels not supporting floor loads.

Figure 6.3.5 Lintels supporting roof, frames and timber floors

Tables

Same wording in ABCB Housing Provisions 2025. See ABCB Housing Provisions 2025 6.3.5.

Clauses referred to