Table · ABCB Housing Provisions 2022

Table 7.4.3a Size of gutter required to drain roof catchment area into one (1) downpipe for various rainfall intensities and roof catchment areas (A, B, C, D, E and F defined in Table 7.4.3b)

Part 7.4 Gutters and downpipes

Open Table 7.4.3a on NCC Online ↗
Design rainfall intensity (mm/h) (as per Table 7.4.3d)Roof catchment area per downpipe — 30 m2Roof catchment area per downpipe — 40 m2Roof catchment area per downpipe — 50 m2Roof catchment area per downpipe — 60 m2Roof catchment area per downpipe — 70 m2
90 mm/hA or CA or CA or CA or CA or C
120 mm/hA or CA or CA or CA or CA or D
140 mm/hA or CA or CA or CA or DB or E
160 mm/hA or CA or CA or CA or EB or E
175 mm/hA or CA or CA or DB or EE
200 mm/hA or CA or CA or DB or EF
225 mm/hA or CA or CA or BEF
255 mm/hA or CA or DB or EEF
275 mm/hA or CA or DB or EFF
325 mm/hA or CB or EFFF
425 mm/hA or CEFFF

Table for 7.4.3 Selection of guttering

Same wording in ABCB Housing Provisions 2025. See ABCB Housing Provisions 2025 Table 7.4.3a.