Deemed-to-Satisfy Provision · NCC 2022 Volume One

C3D10 Separation of classifications in different storeys

Part C3 Compartmentation and separation · NCC 2019: C2.9

Open C3D10 on NCC Online ↗

If parts of different classification are situated one above the other in adjoining storeys they must be separated as follows:

Type A construction — The floor between the adjoining parts must have an FRL of not less than that prescribed in Specification 5 for the classification of the lower storey.

Type B or C construction — If one of the adjoining parts is of Class 2, 3 or 4, the floor separating the part from the storey below must—

be a floor/ceiling system incorporating a ceiling which has a resistance to the incipient spread of fire to the space above itself of not less than 60 minutes; or

have an FRL of at least 30/30/30; or

have a fire-protective covering on the underside of the floor, including beams incorporated in it, if the floor is combustible or of metal.

Same wording in NCC 2025 Volume One. See NCC 2025 Volume One C3D10.