C3D10 Separation of classifications in different storeys
Part C3 Compartmentation and separation · NCC 2019: C2.9
If parts of different classification are situated one above the other in adjoining storeys they must be separated as follows:
Type A construction — The floor between the adjoining parts must have an FRL of not less than that prescribed in Specification 5 for the classification of the lower storey.
Type B or C construction — If one of the adjoining parts is of Class 2, 3 or 4, the floor separating the part from the storey below must—
be a floor/ceiling system incorporating a ceiling which has a resistance to the incipient spread of fire to the space above itself of not less than 60 minutes; or
have an FRL of at least 30/30/30; or
have a fire-protective covering on the underside of the floor, including beams incorporated in it, if the floor is combustible or of metal.