C3D9 Separation of classifications in the same storey
Part C3 Compartmentation and separation · NCC 2019: C2.8
(1) If a building has parts of different classifications located alongside one another in the same storey—
each building element in that storey must have the higher FRL prescribed in Specification 5 for that element for the classifications concerned; or
the parts must be separated in that storey by a fire wall.
(2) A fire wall required by (1)(b) must have the FRL prescribed in accordance with Specification 5 as applicable for that element for the Type of construction and the classifications concerned.
(3) For the purposes of (2), the FRL in Specification 5 must be either—
the higher FRL prescribed in Table S5C11d or S5C21d; or
the FRL prescribed in Table S5C24c.
(4) For the purposes of (1), where one part is a carpark complying with S5C19, S5C22 or S5C25, the parts may be separated by a fire wall complying with S5C19(3)(c), S5C22(3)(c) or S5C25(3)(c) as appropriate.
Clauses referred to
- S5C19 Type A fire-resisting construction — carparks
- S5C22 Type B fire-resisting construction — carparks
- S5C25 Type C fire-resisting construction — carparks