Deemed-to-Satisfy Provision · NCC 2022 Volume One

C3D9 Separation of classifications in the same storey

Part C3 Compartmentation and separation · NCC 2019: C2.8

Open C3D9 on NCC Online ↗

(1) If a building has parts of different classifications located alongside one another in the same storey—

each building element in that storey must have the higher FRL prescribed in Specification 5 for that element for the classifications concerned; or

the parts must be separated in that storey by a fire wall.

(2) A fire wall required by (1)(b) must have the FRL prescribed in accordance with Specification 5 as applicable for that element for the Type of construction and the classifications concerned.

(3) For the purposes of (2), the FRL in Specification 5 must be either—

the higher FRL prescribed in Table S5C11d or S5C21d; or

the FRL prescribed in Table S5C24c.

(4) For the purposes of (1), where one part is a carpark complying with S5C19, S5C22 or S5C25, the parts may be separated by a fire wall complying with S5C19(3)(c), S5C22(3)(c) or S5C25(3)(c) as appropriate.

Same wording in NCC 2025 Volume One. See NCC 2025 Volume One C3D9.
Can't meet C3D9? A Performance Solution must meet the Performance Requirements it satisfies: C1P1, C1P2, C1P3, C1P4, C1P5, C1P6, C1P7, C1P8, C1P9. Start a Performance Solution →

Clauses referred to

Defined terms used