C4D10 Service penetrations in fire-isolated exits
Part C4 Protection of openings · NCC 2019: C3.9
Fire-isolated exits must not be penetrated by any services other than—
electrical wiring permitted by D3D8(6) to be installed within the exit; or
ducting associated with a pressurisation system if it—
is constructed of material having an FRL of not less than –/120/60 where it passes through any other part of the building; and
does not open into any other part of the building; or
for fire services, water supply and test drain pipes.
Changed in NCC 2025. See NCC 2025 Volume One C4D10, or show what changed.
Fire-isolated exits must not be penetrated by any services other … building; or for fire services, water supply and test drain pipes. pipes; or wiring, sensors and the like required for the function and performance of a pressurisation system serving the exit.