Deemed-to-Satisfy Provision · NCC 2022 Volume One
C4D11 Openings in fire-isolated lift shafts
Part C4 Protection of openings · NCC 2019: C3.10
(1) Doorways — If a lift shaft is required to be fire-isolated, an entrance doorway to that shaft must be protected by –/60/– fire doors that—
comply with AS 1735.11; and
are set to remain closed except when discharging or receiving passengers, goods or vehicles.
(2) Lift indicator panels — A lift call panel, indicator panel or other panel in the wall of a fire-isolated lift shaft must be backed by construction having an FRL of not less than –/60/60 if it exceeds 35 000 mm2 in area.
Same wording in NCC 2025 Volume One. See NCC 2025 Volume One C4D11.