Deemed-to-Satisfy Provision · NCC 2022 Volume One
C4D14 Openings in shafts
Part C4 Protection of openings · NCC 2019: C3.13
In a building of Type A construction, an opening in a wall providing access to a ventilating, pipe, garbage or other service shaft must be protected by—
if it is in a sanitary compartment — a door or panel which, together with its frame, is non-combustible or has an FRL of not less than –/30/30; or
a self-closing –/60/30 fire door or hopper; or
an access panel having an FRL of not less than –/60/30; or
if the shaft is a garbage shaft — a door or hopper of non-combustible construction.
Same wording in NCC 2025 Volume One. See NCC 2025 Volume One C4D14.
Can't meet C4D14? A Performance Solution must meet the Performance Requirements it satisfies: C1P1, C1P2, C1P3, C1P4, C1P5, C1P6, C1P7, C1P8, C1P9. Start a Performance Solution →