Deemed-to-Satisfy Provision · NCC 2022 Volume One

C4D13 Openings in floors and ceilings for services

Part C4 Protection of openings · NCC 2019: C3.12

Open C4D13 on NCC Online ↗

(1) Where a service passes through—

a floor that is required to have an FRL with respect to integrity and insulation; or

a ceiling required to have a resistance to the incipient spread of fire,

the service must be installed in accordance with (2).

(2) A service must be protected—

in a building of Type A construction, by a shaft complying with Specification 5; or

in a building of Type B or C construction, by a shaft that will not reduce the fire performance of the building elements it penetrates; or

in accordance with C4D15.

(3) Where a service passes through a floor which is required to be protected by a fire-protective covering, the penetration must not reduce the fire performance of the covering.

Same wording in NCC 2025 Volume One. See NCC 2025 Volume One C4D13.
Can't meet C4D13? A Performance Solution must meet the Performance Requirements it satisfies: C1P1, C1P2, C1P3, C1P4, C1P5, C1P6, C1P7, C1P8, C1P9. Start a Performance Solution →