Deemed-to-Satisfy Provision · NCC 2022 Volume One
C4D13 Openings in floors and ceilings for services
Part C4 Protection of openings · NCC 2019: C3.12
(1) Where a service passes through—
a floor that is required to have an FRL with respect to integrity and insulation; or
a ceiling required to have a resistance to the incipient spread of fire,
the service must be installed in accordance with (2).
(2) A service must be protected—
in a building of Type A construction, by a shaft complying with Specification 5; or
in a building of Type B or C construction, by a shaft that will not reduce the fire performance of the building elements it penetrates; or
in accordance with C4D15.
(3) Where a service passes through a floor which is required to be protected by a fire-protective covering, the penetration must not reduce the fire performance of the covering.