Performance Requirement · NCC 2022 Volume One

D1P3 Fall prevention barriers

Part D1 Access and egress · NCC 2019: DP3

Open D1P3 on NCC Online ↗

(1) A barrier must be provided where people could fall—

1 m or more—

from a floor or roof or through an opening (other than through an openable window) in the external wall of a building; or

due to a sudden change of level within or associated with a building; or

2 m or more from a floor through an openable window—

in a bedroom in a Class 2 or 3 building or a Class 4 part of a building; or

in a Class 9b early childhood centre; or

4 m or more from a floor through an openable window not covered by (b).

(2) A barrier required by (1) must be—

continuous and extend for the full extent of the hazard; and

of a height to protect people from accidentally falling from the floor or roof or through the opening or openable window; and

constructed to prevent people from falling through the barrier; and

capable of restricting the passage of children; and

of strength and rigidity to withstand—

the foreseeable impact of people; and

where appropriate, the static pressure of people pressing against it.

Limitations

D1P3 does not apply where such barrier would be incompatible with the intended use of an area such as a stage, loading dock or the like.

D1P3(2)(d) does not apply to—

fire-isolated stairways, fire-isolated ramps, and other areas used primarily for emergency purposes, excluding external stairways and ramps; and

Class 7 (other than carparks) and Class 8 buildings and parts of buildings containing those classifications.

Same wording in NCC 2025 Volume One. See NCC 2025 Volume One D1P3.