Deemed-to-Satisfy Provision · NCC 2022 Volume One
E1D9 Where sprinklers are required: Class 7a building, other than an open-deck carpark
Part E1 Fire fighting equipment · NCC 2019: Table E1.5
In a Class 7a building, other than an open-deck carpark, sprinklers are required in fire compartments where more than 40 vehicles are accommodated.
Changed in NCC 2025. See NCC 2025 Volume One E1D9, or show what changed.
In a Class 7a building, other than an open-deck carpark, carpark which is a separate building, sprinklers are required in fire compartments where — more than 40 vehicles are accommodated. accommodated; or a carstacker is installed. Notes A carstacker is a machine that stores 2 or more cars in a vertical arrangement such that one or more cars may not be accessible from floor level.
Removed words are struck through; added words are highlighted. Comparison of the text only.
Can't meet E1D9? A Performance Solution must meet the Performance Requirements it satisfies: E1P1, E1P2, E1P3, E1P4, E1P5, E1P6. Start a Performance Solution →