E3D5 Emergency lifts
Part E3 Lift installations · NCC 2019: E3.4
(1) At least one emergency lift complying with (4) must be installed in—
a building which has an effective height of more than 25 m; and
a Class 9a building in which patient care areas are located at a level that does not have direct egress to a road or open space.
(2) An emergency lift may be combined with a passenger lift and must serve those storeys served by the passenger lift so that all storeys of the building served by passenger lifts are served by at least one emergency lift.
(3) Where two or more passenger lifts are installed and serve the same storeys, excluding a lift that is within an atrium and not contained wholly within a shaft—
at least two emergency lifts must be provided to serve those storeys; and
if located within different shafts, at least one emergency lift must be provided in each shaft.
(4) An emergency lift must—
be contained within a fire-resisting shaft in accordance with C3D11; and
in a Class 9a building serving a patient care area—
have minimum dimensions, measured clear of all obstructions, including handrails, etc complying with Table E3D5; and
be connected to a standby power supply system where installed; and
if the building has an effective height of more than 75 m, have a rating of at least—
600 kg if not provided with a stretcher facility; or
900 kg if provided with a stretcher facility.
Table E3D5 Minimum emergency lift dimensions in Class 9a buildings
Lift component
Minimum dimension (mm)
Minimum depth of car
2280
Minimum width of car
1600
Minimum floor to ceiling height
2300
Minimum door height
2100
Minimum door width
1300
Tables
Changed in NCC 2025. See NCC 2025 Volume One E3D5, or show what changed.
(1) At least one emergency lift complying with (4) (5) must be installed in — a building which has an … are served by at least one emergency lift. (3) Where a storey is served by two or more passenger lifts are installed and serve the same storeys, excluding a lift lifts, that is within an atrium and not contained wholly within a shaft — storey must be served by at least two emergency lifts. (4) Where a storey is served by two or more lift shafts, the emergency lifts required by (3) must be provided to serve those storeys; and if located within different shafts, at least one emergency lift must not be provided in each the same shaft. (4) (5) An emergency lift must — be contained within a fire-resisting … height 2300 Minimum door height 2100 Minimum door width 1300