Deemed-to-Satisfy Provision · NCC 2022 Volume One

F3D5 Wall cladding

Part F3 Roof and wall cladding

Open F3D5 on NCC Online ↗

(1) External wall cladding must comply with one or a combination of the following:

Masonry, including masonry veneer, unreinforced and reinforced masonry: AS 3700.

Autoclaved aerated concrete: AS 5146.3.

Metal wall cladding: AS 1562.1.

(2) The following buildings need not comply with (1):

A Class 7 or 8 building where in the particular case there is no necessity for compliance.

A garage, tool shed, sanitary compartment, or the like, forming part of a building used for other purposes, except where the construction of the garage, tool shed, sanitary compartment or the like contributes to the weatherproofing of another part of the building that is required to be weatherproofed.

An open spectator stand or open deck carpark.

Not in NCC 2025. No F3D5 in NCC 2025 Volume One.
Can't meet F3D5? A Performance Solution must meet the Performance Requirements it satisfies: F3P1. Start a Performance Solution →