Deemed-to-Satisfy Provision · NCC 2022 Volume One

F4D8 Construction of sanitary compartments

Part F4 Sanitary and other facilities · NCC 2019: F2.5

Open F4D8 on NCC Online ↗
Varied in VIC. Check the variation for your state.

(1) Other than in an early childhood centre, sanitary compartments must have doors and partitions that separate adjacent compartments and extend—

from floor level to the ceiling in the case of a unisex facility; or

to a height of not less than 1.5 m above the floor if primary school children are the principal users; or

1.8 m above the floor in all other cases.

(2) Unless there is a clear space of at least 1.2 m, measured in accordance with Figure F4D8, between the closet pan within the sanitary compartment and the doorway, the door to a fully enclosed sanitary compartment must—

open outwards; or

slide; or

be readily removable from the outside of the sanitary compartment.

(3) In an early childhood centre, facilities for use by children must have each sanitary compartment screened by a partition which, except for the doorway, is opaque for a height of at least 900 mm but not more than 1200 mm above the floor level.

Figure F4D8 Construction of sanitary compartments

Changed in NCC 2025. See NCC 2025 Volume One F4D8, or show what changed.

(1) Other than in an early childhood centre, sanitary compartments … level to the ceiling in the case of a unisex facility or all gender facility; or to a height of not less than 1.5 … above the floor level. Figure F4D8 Construction of sanitary compartments

Removed words are struck through; added words are highlighted. Comparison of the text only.

State and territory variations all clauses side by side →