F4D7 Accessible unisex showers
Part F4 Sanitary and other facilities · NCC 2019: Table F2.4b
(1) Where required by F4D5(b), the minimum number of accessible unisex showers for each class of building is as follows:
For a Class 1b building—
not less than 1; and
where private accessible unisex showers are provided for every accessible bedroom, common accessible unisex showers need not be provided.
For a Class 2 building, where showers are provided in common areas, not less than 1.
For Class 3 and 9c buildings—
in every accessible sole-occupancy unit provided with showers within the accessible sole-occupancy unit, not less than 1; and
1 for every 10 showers or part thereof provided in common areas.
For Class 5, 6, 7, 8 or 9 buildings, where F4D4 requires 1 or more showers, not less than 1 for every 10 showers or part thereof.
For a Class 10a building, where showers are provided, 1 for every 10 showers or part thereof.
(2) The requirements of (1)(d) do not apply within a ward area of a Class 9a health-care building.
(3) The requirements of (1)(e) do not apply to—
a Class 10a appurtenant to another class of building; and
a sanitary compartment dedicated to a single caravan/camping site.