Deemed-to-Satisfy Provision · NCC 2022 Volume One

F6D12 Kitchen local exhaust ventilation

Part F6 Light and ventilation · NCC 2019: F4.12

Open F6D12 on NCC Online ↗

A commercial kitchen must be provided with a kitchen exhaust hood complying with AS 1668.1 and AS 1668.2 where—

any cooking apparatus has—

a total maximum electrical power input exceeding 8 kW; or

a total gas power input exceeding 29 MJ/hour; or

the total maximum power input to more than one apparatus exceeds, per m2 of floor area of the room or enclosure—

0.5 kW electrical power; or

1.8 MJ/hour gas.

Changed in NCC 2025 (minor wording). See NCC 2025 Volume One F6D12, or show what changed.

A commercial kitchen must be provided with a kitchen exhaust hood system complying with AS 1668.1 and AS 1668.2 where — any … enclosure — 0.5 kW electrical power; or 1.8 MJ/hour gas.

Removed words are struck through; added words are highlighted. Comparison of the text only.

Can't meet F6D12? A Performance Solution must meet the Performance Requirements it satisfies: F6P1, F6P2, F6P3, F6P4, F6P5. Start a Performance Solution →