Deemed-to-Satisfy Provision · NCC 2025 Volume One
F6D12 Kitchen local exhaust ventilation
Part F6 Light and ventilation · NCC 2019: F4.12
A kitchen must be provided with a kitchen exhaust hood system complying with AS 1668.1 and AS 1668.2 where—
any cooking apparatus has—
a total maximum electrical power input exceeding 8 kW; or
a total gas power input exceeding 29 MJ/hour; or
the total maximum power input to more than one apparatus exceeds, per m2 of floor area of the room or enclosure—
0.5 kW electrical power; or
1.8 MJ/hour gas.
Changed since NCC 2022 (minor wording). See NCC 2022 Volume One F6D12, or show what changed.
A commercial kitchen must be provided with a kitchen exhaust hood system complying with AS 1668.1 and AS 1668.2 where — any … enclosure — 0.5 kW electrical power; or 1.8 MJ/hour gas.
Removed words are struck through; added words are highlighted. Comparison of the text only.
Can't meet F6D12? A Performance Solution must meet the Performance Requirements it satisfies: F6P1, F6P2, F6P3, F6P4, F6P5. Start a Performance Solution →