Deemed-to-Satisfy Provision · NCC 2022 Volume One

F6D8 Ventilation borrowed from adjoining room

Part F6 Light and ventilation · NCC 2019: F4.7

Open F6D8 on NCC Online ↗

Natural ventilation to a room may come through a window, opening, door or other device from an adjoining room (including an enclosed verandah) if both rooms are within the same sole-occupancy unit or the enclosed verandah is common property, and—

in a Class 2 building, a sole-occupancy unit of a Class 3 building or Class 4 part of a building—

the room to be ventilated is not a sanitary compartment; and

the window, opening, door or other device has a ventilating area of not less than 5% of the floor area of the room to be ventilated; and

the adjoining room has a window, opening, door or other device with a ventilating area of not less than 5% of the combined floor areas of both rooms; and

in a Class 5, 6, 7, 8 (except a Class 8 electricity network substation) or 9 building—

the window, opening, door or other device has a ventilating area of not less than 10% of the floor area of the room to be ventilated, measured not more than 3.6 m above the floor; and

the adjoining room has a window, opening, door or other device with a ventilating area of not less than 10% of the combined floor areas of both rooms; and

the ventilating areas specified in (a) and (b) may be reduced as appropriate if direct natural ventilation is provided from another source.

Same wording in NCC 2025 Volume One. See NCC 2025 Volume One F6D8.
Can't meet F6D8? A Performance Solution must meet the Performance Requirements it satisfies: F6P1, F6P2, F6P3, F6P4, F6P5. Start a Performance Solution →