F6D8 Ventilation borrowed from adjoining room
Part F6 Light and ventilation · NCC 2019: F4.7
Natural ventilation to a room may come through a window, opening, door or other device from an adjoining room (including an enclosed verandah) if both rooms are within the same sole-occupancy unit or the enclosed verandah is common property, and—
in a Class 2 building, a sole-occupancy unit of a Class 3 building or Class 4 part of a building—
the room to be ventilated is not a sanitary compartment; and
the window, opening, door or other device has a ventilating area of not less than 5% of the floor area of the room to be ventilated; and
the adjoining room has a window, opening, door or other device with a ventilating area of not less than 5% of the combined floor areas of both rooms; and
in a Class 5, 6, 7, 8 (except a Class 8 electricity network substation) or 9 building—
the window, opening, door or other device has a ventilating area of not less than 10% of the floor area of the room to be ventilated, measured not more than 3.6 m above the floor; and
the adjoining room has a window, opening, door or other device with a ventilating area of not less than 10% of the combined floor areas of both rooms; and
the ventilating areas specified in (a) and (b) may be reduced as appropriate if direct natural ventilation is provided from another source.