Deemed-to-Satisfy Provision · NCC 2022 Volume One

F6D7 Natural ventilation

Part F6 Light and ventilation · NCC 2019: F4.6

Open F6D7 on NCC Online ↗

(1) Natural ventilation provided in accordance with F6D6(a) must consist of openings, windows, doors or other devices which can be opened—

with a ventilating area not less than 5% of the floor area of the room required to be ventilated; and

open to—

a suitably sized court, or space open to the sky; or

an open verandah, carport, or the like; or

an adjoining room in accordance with F6D8.

(2) The requirements of (1)(a) do not apply to a Class 8 electricity network substation.

Same wording in NCC 2025 Volume One. See NCC 2025 Volume One F6D7.
Can't meet F6D7? A Performance Solution must meet the Performance Requirements it satisfies: F6P1, F6P2, F6P3, F6P4, F6P5. Start a Performance Solution →