Verification Method · NCC 2022 Volume One

F6V2 Verification of suitable indoor air quality for carparks

Part F6 Light and ventilation · NCC 2019: FV4.2

Open F6V2 on NCC Online ↗

For a Class 7a building, compliance with F6P3 and F6P4(a) is verified when it is determined that the building is provided with sufficient ventilation with outdoor air such that carbon monoxide exposure levels do not exceed the limits specified in Table F6V2.

Table F6V2 Maximum carbon monoxide exposure for carparks

Concentration (ppm)

Total exposure duration per day

100

Not to be exceeded

90

15 minutes

60

1 hour

30

8 hours

Table Notes

Various government work health and safety regulations specify workplace exposure limits for airborne contaminants in the workplace.

Tables

Same wording in NCC 2025 Volume One. See NCC 2025 Volume One F6V2.

Clauses referred to

Defined terms used