Verification Method · NCC 2025 Volume One
F6V2 Verification of suitable indoor air quality for carparks
Part F6 Light and ventilation · NCC 2019: FV4.2
For a Class 7a building, compliance with F6P3 and F6P4(a) is verified when it is determined that the building is provided with sufficient ventilation with outdoor air such that carbon monoxide exposure levels do not exceed the limits specified in Table F6V2.
Table F6V2 Maximum carbon monoxide exposure for carparks
Concentration (ppm)
Total exposure duration per day
100
Not to be exceeded
90
15 minutes
60
1 hour
30
8 hours
Table Notes
Various government work health and safety regulations specify workplace exposure limits for airborne contaminants in the workplace.
Tables
Same wording in NCC 2022 Volume One. See NCC 2022 Volume One F6V2.