Verification Method · NCC 2022 Volume One

F8V1 Condensation management

Part F8 Condensation management · NCC 2019: FV6

Open F8V1 on NCC Online ↗

(1) Compliance with Performance Requirement F8P1 is verified for a roof or external wall assembly when it is determined that a mould index of greater than 3, as defined by Section 6 of AIRAH DA07, does not occur on—

the interior surface of the water control layer; or

the surfaces of building fabric components interior to the water control layer.

(2) The calculation method for (1) must use—

input assumptions in accordance with AIRAH DA07; and

the intermediate method for calculating indoor design humidity in Section 4.3.2 of AIRAH DA07.

Same wording in NCC 2025 Volume One. See NCC 2025 Volume One F8V1.

Clauses referred to

Defined terms used