G2V1 Combustion appliances
Part G2 Boilers, pressure vessels, heating appliances, fireplaces, chimneys and flues · NCC 2019: GV2
Compliance with G2P1(a) and G2P1(b) is verified when—
components used within an appliance and its installation are constructed from—
heat-resistant materials for maximum operating temperatures not less than 600℃, where the material complies with (c); or
heat-tolerant materials for maximum operating temperatures more than 150℃ and less than 600℃, where the material complies with (c); and
the building elements surrounding the appliance maintain their designed function and material properties inclusive of a full range of thermal movements when exposed to the heat effects of the appliance; and
a sample of the material is tested to the maximum operating temperature, specified in (a)(i) or (a)(ii) for a minimum of 96 hours; and
the tested sample, when allowed to cool, is free from—
visible cracks and fractures; and
visible indication of de-lamination; and
linear distortion in excess of the equivalent of 10 mm per metre, and
deterioration of the appearance of any surface finish, when compared to an unheated sample.