Deemed-to-Satisfy Provision · NCC 2022 Volume One
G3D1 Application of Part
Part G3 Atrium construction · NCC 2019: G3.1
This Part does not apply to an atrium which—
connects only 2 storeys; or
connects only 3 storeys if—
each storey is provided with a sprinkler system (other than a FPAA101D or FPAA101H system) complying with Specification 17 throughout; and
one of those storeys is situated at a level at which there is direct egress to a road or open space.
Same wording in NCC 2025 Volume One. See NCC 2025 Volume One G3D1.