NCC 2022 Volume One
Part G3 Atrium construction
5 clauses · Open on NCC Online ↗
- G3D1 Application of PartThis Part does not apply to an atrium which— connects only 2 storeys; or connects only 3 storeys if— each storey is provided with a sprinkler system…
- G3D2 Dimensions of atrium wellAn atrium well must have a width throughout the well that is able to contain a cylinder having a horizontal diameter of not less than 6 m.
- G3D6 Separation at roofIn an atrium— the roof must have the FRL prescribed in Table S5C11g; or the roof structure and membrane must be protected by a sprinkler system…
- G3D7 Means of egressAll areas within an atrium must have access to at least 2 exits.
- G3D8 Fire and smoke control systemsSprinkler systems, smoke control systems, fire detection and alarm systems, and emergency warning and intercom systems must be installed in…