I3D9 Fire hydrants and water supplies
Part I3 Farm buildings and farm sheds · NCC 2019: H3.9
(1) This provision applies to a farm building—
with a total floor area greater than 500 m2; and
located where a fire brigade station is—
not more than 50 km from the building as measured along roads; and
equipped with equipment capable of utilising a fire hydrant.
(2) A farm building referred to in (1) must be—
provided with a fire hydrant system installed in accordance with AS 2419.1, except reference to ‘4 hours’ water supply in clause 4.2 is replaced with ‘2 hours’; or
located on the same allotment as an access point to a water supply which—
has a minimum total capacity of 144,000 litres; and
is situated so as to enable emergency services vehicles access to within 4 m; and
is located within 60 m of the building and not more than 90 m from any part of the building.
(3) For the purposes of (2)(b), water supply for a farm building must consist of one or any number of the following:
A water storage tank.
A dam.
A reservoir.
A river.
A lake.
A bore.
A sea.
(4) If the whole or part of the water supply referred to in (2)(b) is contained in a water storage tank, it must be—
located not less than 10 m from the building; and
fitted with at least one small bore suction connection and one large bore suction connection where—
each suction connection is located in a position so as to enable emergency service vehicles access to within 4 m; and
the suction connections are located not less than 10 m from the building; and
‘small bore suction connection’ and ‘large bore suction connection’ have the meanings contained in AS 2419.1.