Deemed-to-Satisfy Provision · NCC 2025 Volume One

I3D9 Fire hydrants and water supplies

Part I3 Farm buildings and farm sheds · NCC 2019: H3.9

Open I3D9 on NCC Online ↗
Varied in SA. Check the variation for your state.

(1) This provision applies to a farm building —

with a total floor area greater than 500 m2; and

located where a fire brigade station is—

not more than 50 km from the building as measured along roads; and

equipped with equipment capable of utilising a fire hydrant.

(2) A farm building referred to in (1) must be—

provided with a fire hydrant system installed in accordance with AS 2419.1, except reference to ‘4 hours’ water supply in clause 4.2 is replaced with ‘2 hours’; or

located on the same allotment as an access point to a water supply which—

has a minimum total capacity of 144,000 litres; and

is situated so as to enable emergency services vehicles access to within 4 m; and

is located within 60 m of the building and not more than 90 m from any part of the building.

(3) For the purposes of (2)(b), water supply for a farm building must consist of one or any number of the following:

A water storage tank.

A dam.

A reservoir.

A river.

A lake.

A bore.

A sea.

(4) If the whole or part of the water supply referred to in (2)(b) is contained in a water storage tank, it must be—

located not less than 10 m from the building; and

fitted with at least one small bore suction connection and one large bore suction connection where—

each suction connection is located in a position so as to enable emergency service vehicles access to within 4 m; and

the suction connections are located not less than 10 m from the building; and

‘small bore suction connection’ and ‘large bore suction connection’ have the meanings contained in AS 2419.1.

Same wording in NCC 2022 Volume One. See NCC 2022 Volume One I3D9.

State and territory variations all clauses side by side →

Defined terms used