(1) For a Class 5 building, compliance with J1P1 is verified when—

a minimum 5.5-star NABERS Energy base building Commitment Agreement is obtained; and

the energy model required for (a) demonstrates—

the base building’s greenhouse gas emissions are not more than 67% of the 5.5-star level when excluding—

tenant supplementary heating and cooling systems; and

external lighting; and

carparkservices; and

a thermal comfort level of between a Predicted Mean Vote of -1 to +1 is achieved across not less than 95% of the floor area of all occupied zones for not less than 98% of the annual hours of operation of the building; and

the building complies with the additional requirements in Specification 33.

(2) For a Class 2 building, other than sole-occupancy units, compliance with J1P1 is verified when—

a minimum 4-star NABERS Energy for Apartment Buildings Commitment Agreement is obtained; and

air-conditioning, which operates not less than 18 hours per day, is provided to all enclosed common lift lobbies and corridors; and

the energy model required for (a) demonstrates—

the greenhouse gas emissions of the services are less than 90% of the 5-star level; and

a thermal comfort level of between a Predicted Mean Vote of -1 to +1 is achieved across not less than 95% of the floor area of the air-conditioned common area occupied zones, excluding indoor swimming pool chambers, for not less than 98% of the annual hours of operation of the building; and

the space temperature in any indoor swimming pool chamber is maintained at 2°C above the pool temperature during occupied hours of not less than 12 hours per day; and

the building complies with the additional requirements in Specification 33.

(3) For a Class 3 building, compliance with J1P1 is verified when—

a minimum 4-star NABERS Energy for Hotels Commitment Agreement is obtained; and

the operating hours of the services are not less than 12 hours per day in bedrooms, dining rooms and conference facilities, 24 hours per day in corridors and foyers and 18 hours per day in back-of-house areas; and

the energy model required for (a) demonstrates that—

the greenhouse gas emissions of the services are less than 70% of the 5-star level; and

a thermal comfort level of between a Predicted Mean Vote of -1 to +1 is achieved across not less than 95% of the floor area of occupied zones, excluding indoor swimming pool chambers, for not less than 98% of the annual hours of operation of the building; and

the space temperature in any indoor swimming pool chamber is maintained at 2°C above the pool temperature during occupied hours of not less than 12 hours per day; and

the building complies with the additional requirements in Specification 33.

(4) For a Class 6 shopping centre, compliance with J1P1 is verified when—

a minimum 4.5-stars NABERS Energy for Shopping Centres Commitment Agreement is obtained; and

the building has:

an air-conditioned common area of not less than 20% of the gross lettable area; and

a gross lettable area greater than 15 000 m2; and

the energy model required for (a) demonstrates—

the greenhouse gas emissions of the services covered within the scope of NABERS Energy for Shopping Centres ratings are less than 80% of the 4.5-star level; and

a thermal comfort level of between a Predicted Mean Vote of -1 to +1 is achieved across not less than 95% of the floor area of air-conditioned spaces within the scope of the rating for not less than 98% of the annual hours of operation the building; and

the building complies with the additional requirements in Specification 33.

(5) The calculation method for (1), (2), (3) and (4) must comply with ANSI/ASHRAE Standard 140.

Changed in NCC 2025. See NCC 2025 Volume One J1V1, or show what changed.

(1) For a Class 5 building, compliance with J1P1 is verified when — a minimum 5.5-star 6-star NABERS Energy for Offices base building Commitment Agreement is obtained; and the energy model required for (a) demonstrates — that the base building’s regulated energy greenhouse gas emissions are not more than 67% of the 5.5-star level equivalent to at least 6.6-star when excluding — tenant supplementary heating and cooling systems; and external lighting; and carparkservices; carpark services; and the energy model required for (a) demonstrates either — a thermal comfort level of between a Predicted Mean Vote … 98% of the annual hours of operation of the building; or a dry bulb room temperature is maintained across not less than 95% of the floor area of all occupied zones, other than any room containing an indoor swimming pool, for not less than 95% of the annual hours of operation between — 18°C and 25°C for conditioned spaces with transitory occupancy; and 21°C and 24°C for all other conditioned spaces; and the building complies with the additional requirements in Specification 33. (2) For a Class 2 building, other than sole-occupancy units, compliance with J1P1 is verified when — a minimum 4-star NABERS Energy for Apartment Buildings Commitment Agreement is obtained; and air-conditioning, which operates not less than 18 hours per day, is provided to all enclosed common lift lobbies and corridors; and the energy model required for (a) demonstrates — the greenhouse gas emissions of the services are less than 90% of the 5-star level; and a thermal comfort level of between a Predicted Mean Vote of -1 to +1 is achieved across not less than 95% of the floor area of the air-conditioned common area occupied zones, excluding indoor swimming pool chambers, for not less than 98% of the annual hours of operation of the building; and the space temperature in any indoor swimming pool chamber is maintained at 2°C above the pool temperature during occupied hours of not less than 12 hours per day; and the building complies with the additional requirements in Specification 33. (3) For a Class 3 building, compliance with J1P1 is verified … the energy model required for (a) demonstrates that — the regulated energy greenhouse gas emissions of the services are less than 70% of the 5-star level; equivalent to at least 5.3-stars; and a thermal comfort level of between a Predicted Mean Vote of -1 to +1 dry bulb room temperature is achieved maintained across not less than 95% of the floor area of all occupied zones, excluding other than any room containing an indoor swimming pool chambers, pool, for not less than 98% 95% of the annual hours of operation of the building; between — 18°C and 25°C for conditioned spaces with transitory occupancy and food preparation areas; and 21°C and 24°C for all other conditioned spaces; and the space temperature in any indoor swimming pool chamber … the building complies with the additional requirements in Specification 33. (4) (3) For a Class 6 shopping centre, compliance with J1P1 is verified when — a minimum 4.5-stars 6-stars NABERS Energy for Shopping Centres Commitment Agreement is obtained; and … and the energy model required for (a) demonstrates — the regulated energy greenhouse gas emissions of the services covered within the scope of NABERS Energy for Shopping Centres ratings are less than 80% of equivalent to at least 6.7-stars when — excluding carpark services and carpark numbers from NABERS Energy calculation; and calculating solar photovoltaic export based on the 4.5-star level; reduced site energy use arising from (A); and a thermal comfort level of between a Predicted Mean Vote of -1 to +1 dry bulb room temperature is achieved maintained across not less than 95% of the floor area of air-conditioned spaces within the scope of the rating all occupied zones, other than any room containing an indoor swimming pool, for not less than 98% 95% of the annual hours of operation the building; between — 18°C and 25°C for conditioned spaces with transitory occupancy and food preparation areas; and 21°C and 24°C for all other conditioned spaces; and the building complies with the additional requirements in Specification 33. (5) (4) The calculation method for (1), (2), and (3) and (4) must comply with ANSI/ASHRAE Standard 140.

Removed words are struck through; added words are highlighted. Comparison of the text only.

State and territory variations all clauses side by side →

Clauses referred to

Defined terms used