Part J1 Energy efficiency performance requirements · NCC 2019: JV2
(1) For a Class 3, 5, 6, 7, 8 or 9 building, or common area of a Class 2 building, compliance with J1P1 is verified when—
the building complies with the simulation requirements, and is registered, for a Green Star – Design & As-Built or Green Star Buildings rating; and
the annual greenhouse gas emissions of the proposed building are less than 90% of the annual greenhouse gas emissions of the reference building; and
in the proposed building, a thermal comfort level of between a Predicted Mean Vote of -1 to +1 is achieved across not less than 95% of the floor area of all occupied zones for not less than 98% of the annual hours of operation of the building; and
the building complies with the additional requirements in Specification 33.
(2) The calculation method used for (1) must comply with ANSI/ASHRAE Standard 140.
Changed in NCC 2025. See NCC 2025 Volume One J1V2, or show what changed.
(1) For a Class 3, 5, 6, 7, 8 or 9 building, or common area of a Class 2 building, compliance with J1P1 is verified when — the building complies with the simulation requirements, and is registered, for a Green Star – Design & As-Built or Green Star Buildings rating; and the annual greenhouse gas emissions … method used for (1) must comply with ANSI/ASHRAE Standard 140.