NSW I4D13 Flying scenery
NSW Part I4 Entertainment venues other than temporary structures and drive-in theatres
(1) Where there is a grid or other means of flying scenery over a conventional stage or non-conventional stage—
the stage must be provided with a sprinkler system (other than a FPAA101D or FPAA101H system) complying with Specification 17; and
a fly gallery, bridge grid, rigging loft, tie gallery or electric light perch must—
comply with AS 1657; and
be of non-combustible construction; and
a fly gallery must be provided with at least 2 means of egress, one on each side of the stage; and
a grid or rigging loft must be provided with at least 2 means of egress; and
if exposed steel is used in the construction of a roof, fly or tie gallery, the roof, fly or tie gallery must be so designed that, in the event of its structural failure due to fire, the wall structure of the building will not be affected; and
structural steel supporting the stage tower must be enclosed by masonry or concrete and have an FRL of not less than 120/120/120.
(2) In addition to (1), in the case of a conventional stage, the following additional requirements apply:
The proscenium wall must—
have an FRL of not less than 120/120/120; and
have the proscenium opening protected by a rigid safety curtain in accordance with NSW I4D16.
The walls forming the stage area, and the area beneath the stage, must be constructed of masonry or concrete and have an FRL of not less than 120/120/120.