NSW I4D16 Safety curtains — additional requirements
NSW Part I4 Entertainment venues other than temporary structures and drive-in theatres
A rigid safety curtain required by NSW I4D13 must comply with the requirements of NSW I4D15 and it must—
be vertically hung from steel cables; and
be framed with structural steel that complies with AS 4100; and
be sheeted and finished on both sides with sheet steel or other non-combustible material of such gauge, and so fastened to its frame, as to ensure that its frame is capable of withstanding distortion arising from heat; and
when closed, overlap the proscenium opening by not less than 300 mm at each side and by not less than 600 mm at the top.