New South Wales variation · NCC 2022 Volume One

NSW I4D32 Continental seating: egress doorways

NSW Part I4 Entertainment venues other than temporary structures and drive-in theatres

Open on NCC Online ↗

Egress doorways through the walls of the auditorium—

must have an aggregate width of at least twice the sum of the clearances specified in Column 3 of NSW Table I4D29 for each row of the auditorium to be served by those doorways; and

must be provided at each end of every fifth row, excluding the first 2 rows and the last 2 rows in the auditorium if those rows each contain no more than 16 seats; and

must lead—

directly to a road or open space; or

into a foyer or other area giving access to a road or open space; and

must be provided with exit signs if the egress doorways are not sufficiently conspicuous.

Changed in NCC 2025. See NCC 2025 Volume One NSW I4D32, or show what changed.

Delete clause I4D32 and insert NSW I4D32 as follows: Egress doorways through the walls of the auditorium — must … exit signs if the egress doorways are not sufficiently conspicuous.

Removed words are struck through; added words are highlighted. Comparison of the text only.