New South Wales variation · NCC 2022 Volume One

NSW I4D33 Continental seating: clear areas

NSW Part I4 Entertainment venues other than temporary structures and drive-in theatres

Open on NCC Online ↗

A clear area—

must be provided from each end of each row to an egress doorway in the wall of the auditorium; and

must have a width of at least the greater of—

the sum of the clearances specified in Column 3 of NSW Table I4D29 for each row; or

500 mm; and

if it contains platforms or steps, must comply with NSW I4D24(a), (b), (c), (d) and (f).

Changed in NCC 2025. See NCC 2025 Volume One NSW I4D33, or show what changed.

Delete clause I4D33 and insert NSW I4D33 as follows: A clear area — must be provided from each end … must comply with NSW I4D24(a), (b), (c), (d) and (f).

Removed words are struck through; added words are highlighted. Comparison of the text only.