NSW I4D43 Dressing rooms

NSW Part I4 Entertainment venues other than temporary structures and drive-in theatres

Open on NCC Online ↗

A dressing room or two or more adjoining dressing rooms, having a total floor area of more than 50 m2, must—

be separated from other parts of the building by construction having an FRL of not less than 60/60/60; and

have at least 2 means of egress as remote from each other as possible, one of which must discharge—

directly to a road or open space; or

through a fire-isolated exit to a road or open space.