New South Wales variation · NCC 2022 Volume One

NSW I4D51 Electric mains installation: main switchboard

NSW Part I4 Entertainment venues other than temporary structures and drive-in theatres

Open on NCC Online ↗

The switchboard containing the main isolation switch must—

be located in a position that is readily accessible to authorised persons, and to the fire brigade in the case of an emergency; and

be enclosed by construction having an FRL of not less than 60/60/60.