New South Wales variation · NCC 2022 Volume One

NSW I4D59 Automatic smoke-and-heat vents for stages

NSW Part I4 Entertainment venues other than temporary structures and drive-in theatres

Open on NCC Online ↗

An automatic smoke-and-heat vent system required by NSW E2D16(c) for stages and backstages must—

be capable of automatic operation by the inclusion of a heat sensing device designed to activate the system at a temperature of not more than 71°C; and

be capable of being released manually from positions at either side of the stage and of being fully activated from either position; and

have a notice, prominently displayed at each position referred to in (b), clearly indicating the method of activation; and

have an openable area of not less than 10 percent of the total area of the stage.

Changed in NCC 2025. See NCC 2025 Volume One NSW I4D59, or show what changed.

Delete clause I4D59 and insert NSW I4D59 as follows: An automatic smoke-and-heat vent system required by NSW E2D16(c) for … than 10 percent of the total area of the stage.