NSW I4D62 Fuel gas cylinders: enclosures

NSW Part I4 Entertainment venues other than temporary structures and drive-in theatres

Open on NCC Online ↗

An enclosure referred to in NSW I4D61—

must be located not less than 3 m from any window, door, vent or other opening; and

if located 3 m or more from a building must—

have a concrete base; and

be constructed from heavy-gauge chain-wire mesh or other suitable material; and

be at least 1.8 m high; and

be so designed as to securely contain the gas cylinders in a single line; and

be so designed as to allow cross ventilation; and

if located less than 3 m from a building must—

have a concrete base; and

have 3 sides constructed from concrete or masonry; and

have a concrete roof; and

be so designed as to securely contain the gas cylinders in a single line; and

have a hinged, heavy-gauge chain-wire door capable of being secured against unauthorised entry; and

have its roof at least 600 mm above the uppermost fitting of any fuel gas cylinder housed therein.