NSW I4D62 Fuel gas cylinders: enclosures
NSW Part I4 Entertainment venues other than temporary structures and drive-in theatres
An enclosure referred to in NSW I4D61—
must be located not less than 3 m from any window, door, vent or other opening; and
if located 3 m or more from a building must—
have a concrete base; and
be constructed from heavy-gauge chain-wire mesh or other suitable material; and
be at least 1.8 m high; and
be so designed as to securely contain the gas cylinders in a single line; and
be so designed as to allow cross ventilation; and
if located less than 3 m from a building must—
have a concrete base; and
have 3 sides constructed from concrete or masonry; and
have a concrete roof; and
be so designed as to securely contain the gas cylinders in a single line; and
have a hinged, heavy-gauge chain-wire door capable of being secured against unauthorised entry; and
have its roof at least 600 mm above the uppermost fitting of any fuel gas cylinder housed therein.