New South Wales variation · NCC 2022 Volume One

NSW I4D8 Conventional stages: large stages

NSW Part I4 Entertainment venues other than temporary structures and drive-in theatres

Open on NCC Online ↗

A stage which is more than 150 m2 in area—

must have installed directly above the stage a suitable sprinkler system (other than a FPAA101D or FPAA101H system) complying with Specification 17; and

must have the proscenium opening protected by a safety curtain that complies with NSW I4D15 and NSW I4D16; and

must have a line of open drenchers or open sprinklers provided above the proscenium opening on the stage side and in such a position as to be able to discharge over the inside face of the safety curtain; and

must have 2 or more means of egress from the stage and backstage area provided otherwise than through the proscenium wall.

Changed in NCC 2025. See NCC 2025 Volume One NSW I4D8, or show what changed.

Delete clause I4D8 and insert NSW I4D8 as follows: A stage which is more than 150 m2 in area … and backstage area provided otherwise than through the proscenium wall.

Removed words are struck through; added words are highlighted. Comparison of the text only.