New South Wales variation · NCC 2022 Volume One

NSW I5D16 Emergency lighting

NSW Part I5 Temporary structures

Open on NCC Online ↗

Emergency lighting must be provided to the areas provided with artificial lighting under NSW I5D15 and must include a sufficient number of lamps to give a minimum illumination of 0.2 lux at floor level.

Changed in NCC 2025. See NCC 2025 Volume One NSW I5D16, or show what changed.

Delete clause I5D16 and insert NSW I5D16 as follows: Emergency lighting must be provided to the areas provided with … give a minimum illumination of 0.2 lux at floor level.

Removed words are struck through; added words are highlighted. Comparison of the text only.