New South Wales variation · NCC 2022 Volume One

NSW I5D17 Emergency lighting power supply

NSW Part I5 Temporary structures

Open on NCC Online ↗

Where emergency lighting is provided, the capacity of the battery and charging system must be sufficient to provide the illumination required by NSW I5D16 for—

30 minutes, in respect of a temporary structure designed to accommodate not more than 1000 persons; and

60 minutes, in respect of a temporary structure designed to accommodate more than 1000 persons.

Changed in NCC 2025. See NCC 2025 Volume One NSW I5D17, or show what changed.

Delete clause I5D17 and insert NSW I5D17 as follows: Where emergency lighting is provided, the capacity of the battery … a temporary structure designed to accommodate more than 1000 persons.

Removed words are struck through; added words are highlighted. Comparison of the text only.